Matrix M100V Especificações Página 39

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 49
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 38
39
Matrix Installation and Operation Instructions
Menu
Item
Description
Sample HRV
Ventilation
Rates
Installed
Ventilation
Rates
Installed
Fan
Speed
EOH
HRV Exhaust at Override (high ventilation) rate, balanced during High air
circulation rate (800/1000/1200CFM).
120cfm
(55 L/s)
SOH
HRV Supply at Override (high ventilation) rate, balanced during High air
circulation rate (800/1000/1200CFM).
120cfm
(55 L/s)
EOL
HRV Exhaust at Override (high ventilation) rate, balanced during Low air
circulation rate (300/400/500CFM).
120cfm
(55 L/s)
SOL
HRV Supply at Override (high ventilation) rate, balanced during Low air
circulation rate (300/400/500CFM).
120cfm
(55 L/s)
ECH
HRV Exhaust at Continuous (low ventilation) rate, balanced during High air
circulation rate (800/1000/1200CFM).
70cfm
(30 L/s)
SCH
HRV Supply at Continuous (low ventilation) rate, balanced during High air
circulation rate (800/1000/1200CFM).
70cfm
(30 L/s)
ECL
HRV Exhaust at Continuous (low ventilation) rate, balanced during Low air
circulation rate (300/400/500CFM).
70cfm
(30 L/s)
SCL
HRV Supply at Continuous (low ventilation) rate, balanced during Low air
circulation rate (300/400/500CFM).
70cfm
(30 L/s)
Table 11.1 HRV Balancing Table
Magnehelic (0-.25 inwg)
or Digital Manometer
Figure 11.1 Sample Balancing Setup
6” Flow Measurement Station,
Averaging Pitot Tube, or
Pitot TransferTube
Fresh
Supply
Stale
Exhaust
Vista de página 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 48 49

Comentários a estes Manuais

Sem comentários